THLV VOLVO Powered Generator Sets
Power Range: 69kW-520kW
Engine: Volvo (Sweden)
Alternator: MARATHON,ABB,STAMFORD,TELLHOW
Frequency: 50Hz/60Hz -
The generator set comes with VOLVO PENTA (Sweden) engine, with quick and reliable cold start performance, applying advanced optimized combustion process, reduced running expense of continuous load. Optimal designed damper, accurately matched supercharger and low speed cooling fan reduced the noise during gen-set running, and the emission index meets EU Stage-2 Standard.
-
The generator set comes with VOLVO PENTA (Sweden) engine, with quick and reliable cold start performance, applying advanced optimized combustion process, reduced running expense of continuous load. Optimal designed damper, accurately matched supercharger and low speed cooling fan reduced the noise during gen-set running, and the emission index meets EU Stage-2 Standard.
-
We choose VOLVO(Sweden) industrial engine,which enjoys quick and reliable cold start performance.It applies advanced optimized combustion process,which reduces running expence of continuous load.Its optimal designed damper,accurately matched supercharger and low speed cooling fan reduce the noise during running,and the emission index meets EU Stage-2 Standard.
-
The coupled alternator uses TELLHOW, MARATHON,ABB,STAMFORD brushless generator, applying integral salient pole rotor technique, Class H insulation, and steel sheet body, ensuring its advanced performance, steady and reliable operation.
-
Our controller adopts multi-functional control module,which is specific for diesel gen-set. It has Chinese and English operating interface, and automatic/manual control function and kinds of parameter display and protection function. There are different intellectual modules for option,realizing auto-start control,auto-start control + communication,auto-start control + communication + auto paralleling, ATS between mains and generator set,and so on.
Generator set technical parameter |
Engine technical parameter |
|||||||||||
Generator set model |
Prime power |
Standby power |
Dimensions |
Weight |
Engine model |
Cylinders/ |
Bore |
Stroke |
Displacement |
Engine fuel |
Lube volume |
Coolant volume |
(L)×(W)×(H) |
||||||||||||
KW |
KW |
mm |
Kg |
mm |
mm |
L |
g/kw·h |
L |
L |
|||
THLV69 |
69 |
76 |
2500×900×1625 |
1280 |
TAD550GE |
4/L |
108 |
130 |
4.76 |
231 |
13 |
20 |
THLV80 |
80 |
88 |
2500×900×1625 |
1300 |
TAD551GE |
4/L |
108 |
130 |
4.76 |
244 |
13 |
20 |
THLV104 |
104 |
114 |
2805×900×1625 |
1700 |
TAD750GE |
6/L |
108 |
130 |
7.15 |
219 |
20 |
20 |
THLV120 |
120 |
132 |
2805×900×1625 |
1800 |
TAD751GE |
6/L |
108 |
130 |
7.15 |
216 |
20 |
24 |
THLV145 |
145 |
160 |
2600×1275×1665 |
1800 |
TAD752GE |
6/L |
108 |
130 |
7.15 |
205 |
34 |
32 |
THLV160 |
160 |
180 |
2600×1275×1665 |
1860 |
TAD753GE |
6/L |
108 |
130 |
7.15 |
205 |
34 |
32 |
THLV200 |
200 |
220 |
2600×1275×1665 |
1950 |
TAD754GE |
6/L |
108 |
130 |
7.15 |
210 |
34 |
32 |
THLV260 |
260 |
286 |
3000×1275×1780 |
3000 |
TAD1351GE |
6/L |
131 |
158 |
12.78 |
202 |
36 |
44 |
THLV292 |
292 |
321 |
3000×1275×1780 |
3000 |
TAD1352GE |
6/L |
131 |
158 |
12.78 |
197 |
36 |
44 |
THLV300 |
300 |
330 |
3000×1275×1780 |
3000 |
TAD1354GE |
6/L |
131 |
158 |
12.78 |
196 |
36 |
44 |
THLV330 |
330 |
360 |
3000×1275×1780 |
3200 |
TAD1355GE |
6/L |
131 |
158 |
12.78 |
192 |
36 |
44 |
THLV370 |
370 |
407 |
3185×1235×1960 |
3500 |
TAD1650GE |
6/L |
144 |
165 |
16.12 |
202 |
38 |
60 |
THLV400 |
400 |
440 |
3185×1235×1960 |
3500 |
TAD1651GE |
6/L |
144 |
165 |
16.12 |
198 |
38 |
60 |
THLV480 |
480 |
529 |
3370×1460×1982 |
4000 |
TMD1652GE |
6/L |
144 |
165 |
16.12 |
210 |
38 |
118 |
THLV500 |
500 |
550 |
3370×1460×1982 |
4000 |
TMD1653GE |
6/L |
144 |
165 |
16.12 |
208 |
38 |
118 |
THLV520 |
520 |
574 |
3370×1460×1982 |
4100 |
TMD1653GE |
6/L |
144 |
165 |
16.12 |
208 |
38 |
118 |
Generator set technical parameter |
Engine technical parameter |
|||||||||||
Generator set model |
Prime power |
Standby power |
Dimensions |
Weight |
Engine model |
Cylinders/ |
Bore |
Stroke |
Displacement |
Engine fuel |
Lube volume |
Coolant volume |
(L)×(W)×(H) |
||||||||||||
KW |
KW |
mm |
Kg |
mm |
mm |
L |
g/kw·h |
L |
L |
|||
THLV76 |
76 |
83 |
2500×900×1625 |
1150 |
TAD550GE |
4/L |
108 |
130 |
4.76 |
231 |
13 |
20 |
THLV90 |
90 |
99 |
2200×1275×1665 |
1220 |
TAD551GE |
4/L |
108 |
130 |
4.76 |
244 |
13 |
20 |
THLV117 |
117 |
128 |
2600×1275×1665 |
1700 |
TAD750GE |
6/L |
108 |
130 |
7.15 |
219 |
13 |
20 |
THLV137 |
137 |
150 |
2600×1275×1665 |
1800 |
TAD751GE |
6/L |
108 |
130 |
7.15 |
216 |
20 |
24 |
THLV164 |
164 |
180 |
2690×1275×1665 |
1800 |
TAD752GE |
6/L |
108 |
130 |
7.15 |
205 |
34 |
38 |
THLV178 |
178 |
195 |
2690×1275×1665 |
1860 |
TAD753GE |
6/L |
108 |
130 |
7.15 |
205 |
34 |
38 |
THLV201 |
201 |
221 |
2690×1275×1665 |
1950 |
TAD754GE |
6/L |
108 |
130 |
16.12 |
210 |
29 |
32 |
THLV273 |
273 |
300 |
3065×1275×1780 |
3000 |
TAD1351GE |
6/L |
144 |
165 |
16.12 |
202 |
35 |
41 |
THLV320 |
320 |
352 |
3065×1275×1780 |
3000 |
TAD1352GE |
6/L |
144 |
165 |
16.12 |
198 |
35 |
44 |
THLV413 |
413 |
454 |
3350×1235×1960 |
3000 |
TAD1650GE |
6/L |
144 |
165 |
16.12 |
202 |
48 |
44 |
Normal condition: ambient temp:40℃,altitude:1000m,relative humidity:60%.